Review Date Reviewer's Name Type of Review Description Status Comments
03/27/2019 MARTIN BROWN FIRE REVIEW Approved
03/28/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/11/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show that the proposed replacement rooftop units meet the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018.
2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
3. Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2018.
4. Provide smoke detectors in the return air duct, upstream of any outside air connections, for all air distribution systems moving than 2,000 CFM. Reference: Section 606.2.1, IMC 2018, as amended by the City of Tucson.
5. Coordinate the duct distribution schedule with the duct design. SD-1, for example is used for both supply and return openings and the duct sizes do not relate to the airflow rates. Reference: Section 107.2.1, IBC 2018.
04/11/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the specified sensor faucet for the public lavatories has an automatic time-out so that it will dispense a maximum of 0.25 gallons per metering cycle and that the cycle time will last for at least ten seconds for accessibility. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.
3. Revise the location of the expansion tank in the water heater detail so that the shut off valve is not between the water heater and the expansion tank. Reference: Section 607.3, IPC 2018.
04/11/2019 ROBERT SHERRY WATER REVIEW Completed
04/17/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting. Provide evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements, table 401 lighting area and option, 402.1 (light source color temperature requirements), shielding requirements, etc . Do not confuse the Outdoor Lighting Code with the IECC.
2. Provide load calcs, amps and AIC ratings for the existing electrical service. Justify the AIC ratings of the new panels 'A' and 'B'.
Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1.
04/24/2019 DAVID RIVERA ZONING REVIEW Approved
04/30/2019 JOHN VAN WINKLE ENGINEERING REVIEW Approved