Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T19CM02101
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/04/2019 | MASHFOR1 | FIRE | REVIEW | Approved | |
| 04/05/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Please change the current adopted codes on the title sheet to 2017 NEC and International codes to 2018. 2. Please correct the OCPD identification for the new panel 'A' on the existing panel EPHP schedule to 'A'. Ref; 2017 NEC, 2018 IBC sec 107.2.1 |
| 04/09/2019 | QJONES1 | COMMUNICATIONS | REVIEW | Approved | |
| 04/24/2019 | DAVID RIVERA | PLANNING-CITY HALL | REVIEW | Approved | |
| 04/24/2019 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 05/24/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | 1. The City of Tucson has adopted the 2018 International Codes and 2017 National Electric Code , please amend plans to the 2018 IBC and 2017 NEC. IBC 107.2.1. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/07/2019 | PMARTIN1 | OUT TO CUSTOMER | Completed |