Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM02056
Parcel: 132131010

Address:
2985 S KINO PW

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T19CM02056
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/31/2019 ROBERT SHERRY WATER REVIEW Reqs Change 1. Comment not addressed. [Initial comment: The water utility contact is Tucson Water; New Services, Ray Muñoz (520-837-2207).]
2. Comment not addressed. [Initial comment: Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter for buildings that have food service facilities and in locations accessible to Tucson Water. See your civil plans (C9) for an acceptable location. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf]
3. Comment not addressed. [Initial comment: The civil utility plan, C9, Calls for a 2" water meter and a 2" water service to the building while the plumbing schedule and drawings call for a 1-1/2" water service. Coordinate the civil and plumbing drawings. Reference: Section 107.2.1, IBC 2018.]
12/31/2019 LOREN MAKUS ENGINEERING REVIEW Approved
12/31/2019 IMONSHI1 ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/07/2020 PMARTIN1 OUT TO CUSTOMER Completed