Permit Review Detail
Review Status: Active
Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T19CM02028
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/21/2019 | NICHOLAS ROSS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: Nick Ross Lead Planner PROJECT: T19CM02028 620 E. University Blvd New Master and Garage TRANSMITTAL: 3/21/19 COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8). This site is located in the HR-3 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The proposed height of the new master addition is 12' and the proposed setback is 5'11". The required setback is 8'. The proposed height of the new garage is 17' and the proposed setbacks are 2'1" on the east and 1' on the south. The existing garage is over 50 years old and is proposed to be demolished. Historic review is required. |
| 03/21/2019 | NROSS1 | ENGINEERING | REVIEW | Passed | |
| 03/21/2019 | NROSS1 | NPPO | REVIEW | Passed | |
| 03/21/2019 | ANY | BUILDING-RESIDENTIAL | REVIEW | Active |