Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM01949
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/19/2019 | ELISA HAMBLIN | ZONING | REVIEW | Approved | |
| 03/19/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide balancing data for the modified rooms. 2. Provide balancing data and electrical service for the relocated exhaust fan. Reference: Section 507.3, IMC 2018. |
| 03/19/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/19/2019 | EHAMBLI1 | ENGINEERING | REVIEW | Passed | |
| 03/19/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/19/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/19/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise item #6 of the plumbing notes to refer to the 2018 IPC and IECC. There is no such thing as "Section 1070 ASSE". 2. Provide backflow protecton for the ice maker and the coffee maker, if it is connected to water. Reference: sections 608.3 and 608.17.1.2, IPC 2018. |
| 03/19/2019 | MASHFOR1 | FIRE | REVIEW | Approved | Deferred submittal for the fire protection systems will be supplied to TFD per the plan set |
| 03/19/2019 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/28/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 03/28/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 03/28/2019 | QJONES1 | REJECT SHELF | Completed |