Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM01925
Parcel: 117033180

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T19CM01925
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Indicate conduit, conductor sizes and types, quantity, for the existing riser conductors. This is to verify compliance with NEC 230.42.
2. The 1 line diagram shows panel LD rated at 800 amps. This does not correlate with the panel schedule.
Ref; 2017 NEC, 2018 IBC sec 107.2.1.