Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/19/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Indicate conduit, conductor sizes and types, quantity, for the existing riser conductors. This is to verify compliance with NEC 230.42. 2. The 1 line diagram shows panel LD rated at 800 amps. This does not correlate with the panel schedule. Ref; 2017 NEC, 2018 IBC sec 107.2.1. |