Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM01822
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S1-1 (Both Canopies); Design Criteria: This statement indicates the 2015 IBC was used for this design. Please revise to the 2018 IBC, and verify all requirements are met for that code.
2. Sheet S1-1 (Both Canopies); Footings: If the square footing option is used, in addition to the footing size (24" x 24"), please indicate the footing thickness, the footing reinforcing, and the minimum bottom of footing elevation.
3. Sheet S1-1 (60' x 40' Canopy Only); Material List: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the Material List.
4. Structural Calculattions (Both Canopies); Sheet 1: This note indicates the 2015 IBC was used for this design. Please revise to the 2018 IBC, and verify all requirements are met for that code.
5. General: Please provide a Special Inspection Certificate with Parts A and B completed as required.
6. General: Please provide written responses to all review comments.
04/18/2019 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2019 AMARTIN1 OUT TO CUSTOMER Completed