Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM01709
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/21/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Please submit all responses to plan review comments in writting . Plan sheet S2.0 , Detail 1 , Notes #1 W 12x35 Steel Column ; Structural Calculations page 19 states Column W 12x30 , please clarify on plan sheet. IBC 107.2.1 Plan sheet S2.0 , Detail 1 , Notes #2 w 12x30 Steel Beam ; Structural Calculations page 19 states Beam W 12x35 , please clarify on plan sheet . IBC 107.2.1 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/26/2019 | PMARTIN1 | APPROVAL SHELF | Completed |
| 03/26/2019 | PMARTIN1 | OUT TO CUSTOMER | Completed |
| 03/26/2019 | PMARTIN1 | REJECT SHELF | Completed |