Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM01535
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/25/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.2; Restroom Clearances: The plan indicates the door swings out of the restroom, while the actual doors swing in. Please revise, and verify the requirements for the ICC/ANSI Section 603.2.2 (door shall not swing into the 30" x 48" clear floor space) is met.IBC 107.2.1. 2. Sheet A1.2; Restroom Clearances: The elevation of the side wall does not indicate a vertical grab bar per the ICC/ANSI Figure 604.5.1 (or per Sheet A4.0). Please revise. IBC 107.2.1. |
| 04/26/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 04/26/2019 | RMCCOY1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/26/2019 | RMCCOY1 | MECHANICAL-COMMERCIAL | REVIEW | Approved |