Permit Number: T19CM01535
Parcel: 11207168A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM01535
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.2; Restroom Clearances: The plan indicates the door swings out of the restroom, while the actual doors swing in. Please revise, and verify the requirements for the ICC/ANSI Section 603.2.2 (door shall not swing into the 30" x 48" clear floor space) is met.IBC 107.2.1.
2. Sheet A1.2; Restroom Clearances: The elevation of the side wall does not indicate a vertical grab bar per the ICC/ANSI Figure 604.5.1 (or per Sheet A4.0). Please revise. IBC 107.2.1.
04/26/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/26/2019 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Approved
04/26/2019 RMCCOY1 MECHANICAL-COMMERCIAL REVIEW Approved