Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM01535
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/25/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A0.0; Project Data: Effective January 1, 2019, the City of Tucson adopted the 2018 IBC, IMC, IPC, IECC, IFC, and the 2017 NEC. Please revise on this sheet, and verify all requirements and references of the 2018 codes have been met. 2. Sheet A0.0; Project Data: Please add the notation that the accessibility code is the 2009 Edition of the ICC/ANSI. 3. Sheet A0.0; Project Data: The Project Description indicates this is a first time tenant. Is this a new building, and has this space ever had a previous tenant? Please verify. 4. Sheet A0.0; Project Data: Please provide calculations on this sheet for the plumbing fixtures required and provided. Include water closets, lavatories, drinking fountain, and service sink. 5. Sheet A1.2; Restroom Clearances: The plan indicates the door swings out of the restroom, while the actual doors swing in. Please revise, and verify the requirements for the ICC/ANSI Section 603.2.2 (door shall not swing into the 30" x 48" clear floor space) is met. 6. Sheet A1.2; Restroom Clearances: The elevation of the side wall does not indicate a vertical grab bar per the ICC/ANSI Figure 604.5.1 (or per Sheet A4.0). Please revise. 7. Sheet A1.4; Site Plan: Please provide a full site plan for this building. A copy of the site plan from the original shell building permit may be used in each new set. 8. Sheet A2.0 (Floor Plan); Sheet A2.1 (Interior Wall Sections): The wall on the Floor Plan (and in the Wall Legend) do not indicate the specific Wall Section (A, A1, B, C, or D) at each location. Please provide. 9. Sheet A2.0 (Floor Plan); Sheet A2.0 (Wall Legend): The Wall Legend symbol for the existing rated demising wall does not match that wall as shown on the Floor Plan. Please revise. 10. Sheet A3.0 (Reflected Ceiling Plan); Sheet E2.0 (Lighting Plan): Please add a note on the Reflected Ceiling Plan to see the Lighting Plan on Sheet E2.0 for exit lighting locations. 11. Sheet A4.1; Elevation Key Map: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the elevation indicators. 12. General: Please provide written responses to all review comments. |
| 03/28/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/28/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The International Plumbing Code, 2018, is the controlling code for this activity, not the 2012 International Plumbing Code. Reference: Section 101.2, IPC 2018. 2. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate for a minimum time of 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 3. The specification for the BFP calls for a Watts 719QT-S double check valve assembly with a Watts 909AG air gap fitting. The double check valve assembly is listed for non-health hazard applications and it cannot accommodate an air gap fitting. Verify the type of backflow preventer required for this application. Reference: Section 608.1, IPC 2018. 4. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.1, IPC 2018. 5. Floor sinks in the kitchen area or subject to grease waste (e.g. the floor sink near the drop-in cold wells) shall discharge through a grease interceptor. Reference: Section 1003.3, IPV 2018 as amended by the City of Tucson. 6. The specified hydromechanical grease interceptor (Schier GB2) requires the installation of a valve or a flow restriction device on the indirect waste piping when sinks discharge into a floor sink prior to the interceptor. Show how the waste flow into the floor sink will be regulated to prevent an overflow on the kitchen floor. Reference: Sections 303.2 and 1003.3.4.2, IPC 2018. 7. Provide a vent downstream of the specified hydromechanical grease interceptor to protect the seal interceptor. Reference: Section 303.2, IPC 2018. |
| 04/02/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide ventilation calculations based on Section 403.3, IMC 2018. 2. Clarify the area of the kitchen - 340 square feet of 440 square feet. Reference: Section 107.2.1, IBC 2018. 3. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted (i.e. continuous operation during operation of RTU 2). Reference: Section 403.2.1 (4), IMC 2018. |
| 04/03/2019 | ERIC NEWCOMB | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | The City of Tucson has adopted the 2018 International Codes and the 2017 National Electric Code , please amend plans to the 2018 International Codes and the 2017 NEC . IBC 107.2.1. |