Permit Number: T19CM01258
Parcel: 11612009A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM01258
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2019 MASHFOR1 FIRE REVIEW Approved
03/21/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved Please provide full size electrical plans sealed by a Professional Electrical Engineer registered in the State of Arizona.
Ref; City of Tucson Commercial Plan Submittal Requirements.
03/21/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved 1. Sheet PV-1: This sheet must be sealed, signed, and dated by an Arizona licensed professional unless this is a residential project. Please verify.
2. Sheets S1, S2, and S3: These sheets must be sealed, signed, and dated by an Arizona licensed professional engineer.
3. Sheets S1, S2, and S3: Please revise the sheet numbers as required.
4. Sheet S2 (Section B); Structural Calculations (Sheet 2.0): The profile of the carport structure in the calculations does not match the profile on the drawings. Please coordinate.
5. Sheet S2 (Member Sizes Table); Structural Calculations (Sheet 4.12): The calculations indicate a 0.135" thickness for the beam, while the drawing indicates a 0.105" thickness. Please coordinate.
6. Sheet S2 (Pier Footing B1); Structural Calculations (Sheet 6.0): The drilled pier depths differ in the calculations and the Detail B1. Please coordinate.
7. Sheet S2 (Spread Footing B2); Structural Calculations (Sheet 6.3): The footing sizes differ in the calculations and the Detail B2. Please coordinate.
8. Structural Calculations; Sheets 3.3, 3.7, 3.11, 3.19, 3.23, 3.27, and 3.31: The purlins on Sheets 3.3, 3.7, 3.19, and 3.23 indicate a 0.063" thickness for the purlins, while Sheets 3.11, 3.27, and 3.31 indicate 0.058". Please coordinate.
9. General: Please provide the Special Inspection Certificate with Parts A and B completed.
10. General: Please provide written responses to all review comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2019 AVAUGHN1 APPROVAL SHELF Completed
03/15/2019 AVAUGHN1 OUT TO CUSTOMER Completed
03/15/2019 AVAUGHN1 REJECT SHELF Completed