Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM01243
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/05/2019 | MASHFOR1 | FIRE | REVIEW | Approved | Please provide deferred submittal to TFD if the expansion consist of additional sprinkler heaeds or modification to the existing system |
| 03/08/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S1.0 ; 12. Materials of Construction -- Please provide the description for the proposed steel studs . IBC107.2.1. 2. Sheets S1.0 & S2.0 -- Please provide a structural analysis for the proposed 5'1/8"x 13'1/2" GLB. IBC107.2.1 3. Sheet A1 ; Key Notes 6.14 states - "See structural for column sizes" - BUT column sizes are not described and illustrated in the Structural Plans . Please provide column descriptions and illustate on plans . IBC107.2.1. |
| 03/22/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 03/22/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 03/22/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/26/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/01/2019 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
| 04/01/2019 | ANDREW CONNOR | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/12/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 04/12/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 04/12/2019 | QJONES1 | REJECT SHELF | Completed |