Permit Number: T19CM01243
Parcel: 110121080

Address:
5140 E GLENN ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM01243
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2019 MASHFOR1 FIRE REVIEW Approved Please provide deferred submittal to TFD if the expansion consist of additional sprinkler heaeds or modification to the existing system
03/08/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S1.0 ; 12. Materials of Construction -- Please provide the description for the proposed steel studs . IBC107.2.1.
2. Sheets S1.0 & S2.0 -- Please provide a structural analysis for the proposed 5'1/8"x 13'1/2" GLB. IBC107.2.1
3. Sheet A1 ; Key Notes 6.14 states - "See structural for column sizes" - BUT column sizes are not described and illustrated in the Structural Plans . Please provide column descriptions and illustate on plans . IBC107.2.1.
03/22/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/22/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/22/2019 ROBERT SHERRY WATER REVIEW Completed
03/26/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/01/2019 ACONNOR1 ENGINEERING REVIEW Passed
04/01/2019 ANDREW CONNOR ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/12/2019 QJONES1 APPROVAL SHELF Completed
04/12/2019 QJONES1 OUT TO CUSTOMER Completed
04/12/2019 QJONES1 REJECT SHELF Completed