Permit Number: T19CM01191
Parcel: 10510010D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM01191
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2019 STEVE SHIELDS ZONING REVIEW Approved
02/19/2019 GPERU1 MECHANICAL-COMMERCIAL REVIEW Completed
02/19/2019 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide written responses to all plan review comments:
1. Indicate the circuit designation and wiring method for the new tankless water heater.
02/19/2019 SSHIELD1 ENGINEERING REVIEW Passed
02/19/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/19/2019 GPERU1 WATER REVIEW Reqs Change
02/19/2019 GPERU1 PLUMBING-COMMERCIAL REVIEW Reqs Change Please provide written responses to all plan review comments.
1. Please show and provide the routing for T&P for new water heater if required by water heater manufacturer. IPC 504.4
2. The water supply connection to the coffee maker machine requires protection against backflow by a back-flow preventer conforming to ASSE 1022 or ASSE 1024, or protected by an air gap. IPC 608.17.1.2
3. Provide the size and description of the existing water meter for verification of adequate service capacity for new plumbing fixtures. IPC 603.1
02/19/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/20/2019 MASHFOR1 FIRE REVIEW Approved