Permit Number: T19CM01180
Parcel: 136048090

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T19CM01180
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2020 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Approved Reviewer: Chris Anderson, October 22, 2019
BUILDING - COMMERCIAL
1. The "Secondary Elevation at 6" on page 20 and 28 does not match the approved architectural elevations. There are no windows on the architectural elevations. Coordinate with the Architect.
2. The "Secondary Elevation at A" on page 23 and 31 does not match the approved architectural elevations. The architectural drawings show rectangular windows with tops at 16'-0" AFF while the Varco Pruden shop drawings show square windows with tops below 7'-6" AFF. Coordinate with the Architect.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/05/2020 JGARCIA1 APPROVAL SHELF Passed
06/05/2020 JGARCIA1 OUT TO CUSTOMER Completed
06/05/2020 JGARCIA1 REJECT SHELF Completed