Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T19CM01180
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/05/2020 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Approved | Reviewer: Chris Anderson, October 22, 2019 BUILDING - COMMERCIAL 1. The "Secondary Elevation at 6" on page 20 and 28 does not match the approved architectural elevations. There are no windows on the architectural elevations. Coordinate with the Architect. 2. The "Secondary Elevation at A" on page 23 and 31 does not match the approved architectural elevations. The architectural drawings show rectangular windows with tops at 16'-0" AFF while the Varco Pruden shop drawings show square windows with tops below 7'-6" AFF. Coordinate with the Architect. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/05/2020 | JGARCIA1 | APPROVAL SHELF | Passed |
| 06/05/2020 | JGARCIA1 | OUT TO CUSTOMER | Completed |
| 06/05/2020 | JGARCIA1 | REJECT SHELF | Completed |