Permit Number: T19CM01141
Parcel: 10509550A

Address:
4861 N STONE AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM01141
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2019 LMAKUS1 ZONING REVIEW Passed
02/15/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide cooling/heating load calculations for the new rooftop units
2. Provide the ventilation calculations referenced in the equipment schedule
3. Revise the condensate drain termination in the detail to be to an indirect waste.
4. The current code is the 2018 IMC, not the 2012 IMC
02/15/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/15/2019 LOREN MAKUS ENGINEERING REVIEW Passed
02/15/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/15/2019 ROBERT SHERRY WATER REVIEW Completed
02/15/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify the size of the gas pipe serving RTU-5 & RTU-6; RTU-8 & RTU-9
02/15/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
02/21/2019 QJONES1 FIRE REVIEW Needs Review