Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/15/2019 | LMAKUS1 | ZONING | REVIEW | Passed | |
02/15/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide cooling/heating load calculations for the new rooftop units 2. Provide the ventilation calculations referenced in the equipment schedule 3. Revise the condensate drain termination in the detail to be to an indirect waste. 4. The current code is the 2018 IMC, not the 2012 IMC |
02/15/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/15/2019 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
02/15/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/15/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
02/15/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Verify the size of the gas pipe serving RTU-5 & RTU-6; RTU-8 & RTU-9 |
02/15/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
02/21/2019 | QJONES1 | FIRE | REVIEW | Needs Review |