Permit Number: T19CM01138
Parcel: 13824023J

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM01138
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
04/02/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/02/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref: Outdoor Lighting Calcs.
(a) The proposed Special Inspector for outdoor lighting is not on the Approved List. See the Pima County List of approved special inspectors for lighting.
(b) Verify compliance with section 403.5 for the unshielded luminaires.
Ref; 2012 Tucson/Pima County Outdoor Lighting Code, Pima County Special Inspectors list.
04/02/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the location of the regulator shown on detail 5/P4.1 to agree with the gas schematic on sheet P3.1. [Initial comment: Southwest Gas, the local gas utility, provides natural gas at 7" WG, 2 PSIG, and 5 PSIG. Appliances needing gas service at 7" WG or greater (e.g. the fryers and the griddle) will require a gas meter that delivers at least 2 PSIG gas into a regulator located after the meter set. Clarify the location of the regulator. Reference: Section 402.1, IFGC 2018.]
2. Revise the geometry of the sediment trap per Section 408.4, IFGC 2018. [Initial comment: Revise the configuration of the natural gas trap, as shown in detail 1/P4.1, to comply with the requirements of Section 408.4, IFGC 2018 (i.e. the sediment trap is to be located downstream of the appliance shutoff valve, as close to the appliance as possible).]
04/04/2019 AVAUGHN1 ZONING REVIEW Needs Review
04/04/2019 AVAUGHN1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/04/2019 AVAUGHN1 APPROVAL SHELF Completed
04/04/2019 AVAUGHN1 OUT TO CUSTOMER Completed
04/04/2019 AVAUGHN1 REJECT SHELF Completed