Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T19CM01138
Parcel: 13824023J

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T19CM01138
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2019 MARTIN BROWN FIRE REVIEW Approved
03/04/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet T-1; Code Review Checklist (Allowable Area): The allowable area indicates 28,500 SF, with a 75% increase for frontage. Please show the frontage calculations (per the IBC Sections 506.3.2 and 506.3.3) on this sheet.
2. Sheet T-1; Code Review Checklist (Allowable Area): Using the area increase for frontage, please provide a calculation on this sheet for the total allowable SF (Table 506.2 + frontage increase).
3. Sheet C-1: Please darken the lettering on this sheet.
4. Sheet C-1; Dumpster Enclosure Section 6: Since the wall is greater than 7' in height, please provide structural calculations for the dumpster enclosure wall and foundation.
5. Sheet C-1; Dumpster Enclosure Section 6: A note for the wall indicates "6" concrete slab with fiberglass reinforcing". Please remove that note.
6. Sheet ADA-1: Please darken the lettering on this sheet.
7. Sheet ADA-1: Please add a detail on this sheet for the drinking fountain spout location per the ICC/ANSI Figure 602.5.
8. Sheet A-1; Life Safety Plan: Please provide calculations on this sheet for the number of required accessible dining surfaces per the IBC Section 1108.2.9.1 (7 are indicated on that plan).
9. Sheet A-2.0; Wall Type Details: A note on Detail 1 indicates to see the plan for the standard stud sizes. Where are those located?
10. Sheet A-3; Elevations: The titles for Elevations 1 and 3 are reversed (direction). Please revise.
11. Sheet A-8; Building Sections 1 and 2: Please add the grid lines to the sections (per Sheet A-2.0).
12. Sheet A-9; Building Sections 1, 2, and 3: Please add the grid lines to the sections (per Sheet A-2.0).
13. Sheet S-3.1; Roof Framing Plan: Please add a note at the southwest corner to reference Sheet A-10.1 for the roof hatch and the roof access ladder details.
14. Sheet S-4.1; Detail 109: The dumpster enclosure Section 6 on Sheet C-1 indicates a wall different from Detail 109. Please coordinate.
15. General: Please darken the lettering as required on all sheets.
16. General: Please provide the Special Inspections Certificate with Parts A and B completed.
17. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
03/05/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The civil utility plan cannot be "for reference only" as it is the document that will be used to construct the building sewer and water service to the building. Reference: Section 107.2.1, IBC 2018.
2. Provide sheet FS-2 as noted on sheets P1.2 and P2.1.
3. Southwest Gas, the local gas utility, provides natural gas at 7" WG, 2 PSIG, and 5 PSIG. Appliances needing gas service at 7" WG or greater (e.g. the fryers and the griddle) will require a gas meter that delivers at least 2 PSIG gas into a regulator located after the meter set. Clarify the location of the regulator. Reference: Section 402.1, IFGC 2018.
4. Revise the configuration of the natural gas trap, as shown in detail 1/P4.1, to comply with the requirements of Section 408.4, IFGC 2018 (i.e. the sediment trap is to be located downstream of the appliance shutoff valve, as close to the appliance as possible).
5. Verify that the specified automatic faucets for the lavatories will dispense a maximum of 0.25 gallons per metering cycle and that cycle will operate for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
6. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.
7. Provide a low-pressure cutoff for the booster pump per Section 606.5.5, IPC 2018.
8. Appliances (e.g. soda dispensers, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2018.
9. The rim elevation of the next upstream sanitary manhole (2478.95') is higher than the first floor elevation (2478.42'). Provide a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.
10. Coordinate the design of the roof drainage with the architect; keynote 3 and detail 2/A-4 shows primary and secondary roof drains as well as overflow scuppers; the building sections on A-8 and A-9 show 6" primary and secondary roof drains. Reference: Section 107.2.1, IBC 2018.
03/05/2019 ROBERT SHERRY WATER REVIEW Completed
03/06/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1, IECC 2018.
2. Clarify why the specifications for the roof top units show a gross cooling capacity of 180 MBH while the mechanical COMcheck description shows a 210 MBH cooling capacity. Reference: Section 107.2.1, IBC 2018.
3. Revise the COMcheck Envelope Compliance Certificate to show reduced lighting power as the means of Section C406 compliance as the mechanical and interior lighting COMcheck analyses have done. Reference: Section 107.2.1, IBC 2018.
03/11/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet E7.2. The outdoor lighting calcs show total lumens for the Dutch Brothers Building. Please clarify.
2. Indicate whether a special inspection is required for outdoor lighting. Sec 104.2.2, 106.2.
Ref; 2012 Tucson/Pima County Outdoor Lighting Code.
03/20/2019 NICHOLAS ROSS ZONING REVIEW Reqs Change DP19-0040 must be approved first
03/26/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T19CM01138

1) Coordinate with Development Package DP18-0298 to ensure that roof drains scupper underneath sidewalks. Reference City of Tucson Technical Standards Manual (TSM) section 7-01.4.1.E
2) Engineering can review the building plans over the counter once the above comments and any outstanding commercial reviews have been completed

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007

Final Status

Task End Date Reviewer's Name Type of Review Description
03/28/2019 AMARTIN1 OUT TO CUSTOMER Completed