Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM01102
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/31/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | T19CM01102 1) Engineering has reviewed the building plans and they appear to be in conformance with the unapproved development plan. Once the Development Plan has been approved, and all outstanding department reviews are complete, Engineering can approve the building plans 2) Please denote the development plan sheets as "FOR REFERENCE ONLY", since they are not the approved development plan set John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov 520-837-5007 |
| 05/31/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed. [Initial comment: Provide energy code compliance calculations for the addition to the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C402, C502.1, International Energy Conservation Code 2018.] |
| 05/31/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide manufacture cut sheet for the 'SB' luminaire. Be advised that the rated light source color temperature output cannot exceed 3500K for the exterior lighting, per section 402.1. Please verify. Ref; 2018 IBC sec 107.2.1, 2017 NEC, Tucson/Pima County Outdoor Lighting Code. |
| 05/31/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Roof drainage calculations and drainage design not provided. [Initial comment: General Note #3 on sheet A2.2 refers to roof drainage calculations on sheet P2.1. Provide the roof drainage calculations and drainage design.] |
| 06/04/2019 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T19CM01102 - Expansion to existing carwash building (Commercial Use- Special Exception) Building Plan Review (1st Review) Dynamite Carwash 5071 S. 12th Avenue - C-1 Zoning - Related to DP19-0042 & T10SE00119 TRANSMITTAL DATE: June 4, 2019, 2019 DUE DATE: May 1, 2019 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the Building plans for compliance with the unapproved version of the development package on the first submittal. While the building footprint and the site revisions were consistent with the unapproved version of the DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc.) zoning could approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans and the DP is approved. (As of this building review the DP has not been reviewed by the CDRC reviewers.) 2. COMMENT: Zoning will review the building plans on the next submittal and do a comparison to the approved DP if available to assure consistency with what is proposed on the DP drawings as it relates to the zoning review purview as noted above and any conditions related to the change of PDP. 3. COMMENT: If any changes are necessary to the building plans due to plan review comments that affect zoning requirements the DP will have to be revised to reflect the changes. Once the DP is approved by all reviewers and the building plans are approved by the Commercial Plans reviewers zoning can approve the building plans. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/26/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 06/26/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 06/26/2019 | QJONES1 | REJECT SHELF | Completed |