Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM01101
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2019 | ALEXANDRA HINES | ZONING | REVIEW | Approved | |
| 02/14/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a design for the exhaust duct, including height above the roof and any needed bracing. 2. Show that the exhaust duct is at least 30-feet from the property line. Reference: Section 501.3.1, IMC 2018. 3. Show how adequate make up air will be introduced into the room. Reference: Section 501.4, IMC 2018. 4. Provide the quantity of product that will be on site (stored open, stored closed, and in use). Provide a design for the storage area. Reference: Section 502.9.5, IMC 2018. |
| 02/14/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 02/14/2019 | AHINES2 | ENGINEERING | REVIEW | Passed | |
| 02/14/2019 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Please provide written responses to all plan review comments. 1. Please determine the occupancy classification for the paint booth area; specify the fire resistance classification for the interior wall that separates the office(s) from the space containing the paint booth. IBC TABLE 508.4 2. The construction of a fire resistance wall will need to be designed to a UL listing or TABLE 721.1(2). Specify if wall is to be constructed as a fire barrier or fire wall. 3. The common path of egress travel cannot exceed 75 ft. in a F-1 occupancy; please verify that this requirement is in compliance by providing distances for exit travel. IBC 1006.2.1. 4. A drainking fountain for ADA and standing person use is required along an accessible route. IBC TABLE 2902.1 5. A service sink is required; show location or lable as existing if one is located in the building. IBC TABLE 2902.1 |
| 02/14/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/22/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Electrical wiring methods in hazardous are to comply with NEC 500 articles for hazardous locations. 2. The electrical design needs to be designed and sealed by an Electrical Engineer registered in the State of AZ. Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Electrical Plan Submittal Requirements. |
| 02/22/2019 | QJONES1 | FIRE | REVIEW | Needs Review | |
| 02/22/2019 | QJONES1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/22/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 02/22/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 02/22/2019 | QJONES1 | REJECT SHELF | Completed |