Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM01077
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2019 | ALEXANDRA HINES | ZONING | REVIEW | Approved | |
| 02/14/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The 2018 IECC is the current code applying to the energy aspects of the envelope alterations (see door/window general notes, A4.0). 2. Provide an energy analysis for the envelope alterations to verify that the work complies with the 2018 IECC (e.g. COMcheck). |
| 02/14/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide for the grounding electrode system to be common for both services on this building as required per NEC 250.58. |
| 02/14/2019 | AHINES2 | ENGINEERING | REVIEW | Passed | |
| 02/14/2019 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | The adopted code for the City of Tucson as of Jan. 1, 2019 is the 2018 International Building Code. The structural plans and calculations are required to be designed in accordance with the 2018 International Building Code. |
| 02/14/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/14/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 02/14/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/21/2019 | AVAUGHN1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |