Permit Number: T19CM01036
Parcel: 12107002A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T19CM01036
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2019 RSHERRY1 ZONING REVIEW Needs Review
04/17/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify the piping sizes and revise the note calling for 7" WC from the pressure regulator. [Initial comment: Based upon Table 402.4 (2), IFGC 2018, a 1-1/4" carbon steel pipe is required for the pipe serving the six radiant heaters (a 1" pipe can serve a maximum of 173 CFH at 125-feet).]
04/17/2019 ROBERT SHERRY BUILDING-COMMERCIAL REVIEW Needs Review
04/17/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Replot the registrant's seal