Review Details: RESUBMITTAL - TI ALL
Permit Number - T19CM01036
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/17/2019 | RSHERRY1 | ZONING | REVIEW | Needs Review | |
| 04/17/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify the piping sizes and revise the note calling for 7" WC from the pressure regulator. [Initial comment: Based upon Table 402.4 (2), IFGC 2018, a 1-1/4" carbon steel pipe is required for the pipe serving the six radiant heaters (a 1" pipe can serve a maximum of 173 CFH at 125-feet).] |
| 04/17/2019 | ROBERT SHERRY | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 04/17/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Replot the registrant's seal |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/18/2019 | AVAUGHN1 | APPROVAL SHELF | Completed |
| 04/18/2019 | AVAUGHN1 | OUT TO CUSTOMER | Completed |
| 04/18/2019 | AVAUGHN1 | REJECT SHELF | Completed |