Permit Number: T19CM00929
Parcel: 13615041A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM00929
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/07/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The site plan (A1) shows numerous existing PV arrays on this parcel. The electrical line diagrams for this activity only shows the new proposed PV array interconnection to an existing service. Provide a plaque or directory at each electrical service on the premises as required per NEC art 705.10
2. Provide details for the racking system.
3. Provide grounding and bonding details at the columns, inverters, PV panels, racking.
4. Provide more detail or indicate wiring methods utilized for extending the lighting circuits to the new under canopy lighting. Also provide shielding information for the under canopy lighting.
Ref; 2018 IBC sec 107.2.1, 2017 NEC.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/15/2019 AVAUGHN1 APPROVAL SHELF Completed
03/15/2019 AVAUGHN1 OUT TO CUSTOMER Completed
03/15/2019 AVAUGHN1 REJECT SHELF Completed