Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM00929
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/01/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/07/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The site plan (A1) shows numerous existing PV arrays on this parcel. The electrical line diagrams for this activity only shows the new proposed PV array interconnection to an existing service. Provide a plaque or directory at each electrical service on the premises as required per NEC art 705.10 2. Provide details for the racking system. 3. Provide grounding and bonding details at the columns, inverters, PV panels, racking. 4. Provide more detail or indicate wiring methods utilized for extending the lighting circuits to the new under canopy lighting. Also provide shielding information for the under canopy lighting. Ref; 2018 IBC sec 107.2.1, 2017 NEC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/15/2019 | AVAUGHN1 | APPROVAL SHELF | Completed |
| 03/15/2019 | AVAUGHN1 | OUT TO CUSTOMER | Completed |
| 03/15/2019 | AVAUGHN1 | REJECT SHELF | Completed |