Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T19CM00923
Parcel: 13623008Q

Address:
3455 S WILMOT RD

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T19CM00923
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2019 AMARTIN1 COMMUNICATIONS REVIEW Completed
02/13/2019 MASHFOR1 FIRE REVIEW Approved
02/28/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet C-5; Section A: The title for this section indicates A/C4. Please revise.
2. Structural Calculations; Cover Page: A statement on this page indicates the analysis was performed in accordance with the 2012 IBC. Please revise the statement and the calculations to comply with the 2018 IBC (as stated on Drawing Sheet T-1).
3. Structural Calculations; Tower Modification Drawings: The structural drawings for the tower extension must be submitted on full sized sheets (matching the other submittal sheets). Please provide two sets.
4. General: Please provide a Special Inspection Certificate with Parts A and B completed. Follow the IBC Chapter 17 for the required special inspections.
5. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
03/05/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; plan sheet E-1A,
(a) One Line Diagram, Note. The fault current rating of the equipment is part of the electrical design and should be calculated by the design professional (Registrant of Record) not the contractor. Please revise the drawing to show the available fault current calcs, available fault current at the Service and associated equipment and ratings downstream.
(b) Provide for 2 ground rods grounding the electrical service or show the Service Grounding Electrode Conductor connected to the Ground Ring. NEC 250.53A(2).
Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
04/04/2019 AMARTIN1 PLANNING-CITY HALL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/04/2019 AMARTIN1 OUT TO CUSTOMER Completed