Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T19CM00923
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/11/2019 | AMARTIN1 | COMMUNICATIONS | REVIEW | Completed | |
| 02/13/2019 | MASHFOR1 | FIRE | REVIEW | Approved | |
| 02/28/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet C-5; Section A: The title for this section indicates A/C4. Please revise. 2. Structural Calculations; Cover Page: A statement on this page indicates the analysis was performed in accordance with the 2012 IBC. Please revise the statement and the calculations to comply with the 2018 IBC (as stated on Drawing Sheet T-1). 3. Structural Calculations; Tower Modification Drawings: The structural drawings for the tower extension must be submitted on full sized sheets (matching the other submittal sheets). Please provide two sets. 4. General: Please provide a Special Inspection Certificate with Parts A and B completed. Follow the IBC Chapter 17 for the required special inspections. 5. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 03/05/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; plan sheet E-1A, (a) One Line Diagram, Note. The fault current rating of the equipment is part of the electrical design and should be calculated by the design professional (Registrant of Record) not the contractor. Please revise the drawing to show the available fault current calcs, available fault current at the Service and associated equipment and ratings downstream. (b) Provide for 2 ground rods grounding the electrical service or show the Service Grounding Electrode Conductor connected to the Ground Ring. NEC 250.53A(2). Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
| 04/04/2019 | AMARTIN1 | PLANNING-CITY HALL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/04/2019 | AMARTIN1 | OUT TO CUSTOMER | Completed |