Permit Number: T19CM00903
Parcel: 132130610

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM00903
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/22/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The COMcheck component description calls out R19 cavity insulation in the walls along with R-25 continuous insulation. The R-19 cavity insulation is shown in the building sections but the continuous insulation is not shown. Similarly, the roof insulation on COMcheck does not match the drawings. [Initial comment: Provide calculations for the building envelope to demonstrate compliance with the energy code (e.g. COMcheck - the information on sheet T1.2 appears to be for a different building). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. As a minimum, the information shall include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2018.]
11/22/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved