Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2019 MASHFOR1 FIRE REVIEW Approved Fire Alarm is required and noted on the plan set as a deferred submittal
04/05/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide Structural Calculations for the Pre-Engineered Metal Building . IBC 107.2.1.
2. Provide Structural Calculations for the proposed footings , foundation , and anchoring design of the Foundation Plan for the Pre-Engineered Metal Building . IBC 107.2.1.
3. Sheet S2.2 , Detail 35 / S8.3 is not located on sheet S8.3 . Please clarify . IBC 107.2.1.

Please respond in writing to all plan review comments .
04/15/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/15/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide calculations for the building envelope to demonstrate compliance with the energy code (e.g. COMcheck - the information on sheet T1.2 appears to be for a different building). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. As a minimum, the information shall include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2018.
2. Provide heating load calculations to justify the heating capacities of the specified unit heaters. Reference: Section C403.1.1, IECC 2018.
3. Replot sheet M1.1 so that the background is visible. Reference: Section 107.2.1, IBC 2018.
04/15/2019 ROBERT SHERRY WATER REVIEW Passed
04/25/2019 ALEXANDRA HINES ZONING REVIEW Approved
04/30/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet E1.2. The outdoor lighting lumen calcs on the top of the plan do not correlate with the calcs at the bottom of the plan. Please clarify.
2. Provide a note requiring a special inspection for the outdoor lighting as specified per section 104.2.2.
3. Provide manufacture cut sheets for the SA, SB, and A luminaires.
4. Ref; Plan Sheet E1.1. The panel marked L1C is not marked as existing. Is this also a new panel? Please clarify.
5. Provide complete electrical plans for the exterior lighting. Show designated branch circuit numbers and panel.
Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code.
05/01/2019 LOREN MAKUS ENGINEERING REVIEW Approved
05/06/2019 PMARTIN1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/13/2019 AVAUGHN1 OUT TO CUSTOMER Completed