Permit Number: T19CM00866
Parcel: 117042070

Address:
44 W 6TH ST #01

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM00866
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2019 ELISA HAMBLIN ZONING REVIEW Approved
02/05/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/05/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/05/2019 MARTIN BROWN FIRE REVIEW Approved
02/05/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the plumbing plan to locate the lavatory inside of the toilet room. Coordinate with the architect. Reference: Section 405.3.2, IPC 2012.
2. Provide a metering faucet for the relocated lavatory.
3. Provide tempered water for the lavatory.
02/05/2019 ROBERT SHERRY WATER REVIEW Completed
02/06/2019 AVAUGHN1 BUILDING-COMMERCIAL REVIEW Needs Review
02/06/2019 AVAUGHN1 ENGINEERING REVIEW Needs Review
02/06/2019 AVAUGHN1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/06/2019 AVAUGHN1 APPROVAL SHELF Completed
02/06/2019 AVAUGHN1 OUT TO CUSTOMER Completed
02/06/2019 AVAUGHN1 REJECT SHELF Completed