Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T19CM00864
Parcel: 116206290

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM00864
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/06/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/06/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/06/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed