Permit Number: T19CM00703
Parcel: 12108065F

Address:
1401 N ROOK AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM00703
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2019 ELISA HAMBLIN ZONING REVIEW Approved
01/31/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide REScheck analysis of the building addition.
2. Provide tamper-proof refrigeration connections for the condensing unit.
3. Provide secondary condensate drain for the air handler.
4. Show how the mechanical ventilation will be provided.
5. Provide maintenance access to the fan-coil unit.
6. Provide a detail showing how the fan-coil will be supported from the building structure.
01/31/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/31/2019 EHAMBLI1 ENGINEERING REVIEW Passed
01/31/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Clear up drafting issues.
01/31/2019 ROBERT SHERRY WATER REVIEW Reqs Change Provide the total demand that the existing 3/4" water meter will serve.
01/31/2019 MASHFOR1 FIRE REVIEW Approved
02/21/2019 GPERU1 BUILDING-COMMERCIAL REVIEW Approved
02/21/2019 GPERU1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/21/2019 QJONES1 APPROVAL SHELF Completed
02/21/2019 QJONES1 OUT TO CUSTOMER Completed
02/21/2019 QJONES1 REJECT SHELF Completed