Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM00689
Parcel: 117110170

Address:
177 N CHURCH AV

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T19CM00689
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/20/2019 MARTIN BROWN FIRE REVIEW Approved
02/25/2019 ROBERT SHERRY BUILDING-COMMERCIAL REVIEW Reqs Change The 2018 International Building Code with Local Amendments is the relevant code for this project. Revise the calculations and compliance notes on the drawings as needed.
03/01/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please revise cover sheet to reflect the current adopted electrical code. 2017 NEC
03/27/2019 QJONES1 COMMUNICATIONS REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/27/2019 QJONES1 APPROVAL SHELF Completed
03/27/2019 QJONES1 OUT TO CUSTOMER Completed
03/27/2019 QJONES1 REJECT SHELF Completed