Permit Number: T19CM00644
Parcel: 133382660

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T19CM00644
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2019 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed
03/04/2019 MARTIN BROWN FIRE REVIEW Reqs Change This residence will have a "fire-flow calculation area"(2018 IFC Appendix B, Section B102 and 105.1) greater than 3,600 sq. ft.: therefore this house will require a residential sprinkler system unless the fire flow in the nearest hydrant is a minimum of 1,750 GPM for 2 hours duration at 20 psi residual pressure. Additionally, the hydrant must be within 600' of all parts of the residence. Contact Tucson Water and request a "modeled" fire flow for this address. Provide notes on plan and correspondence from Tucson Water regarding verification of fire flow and or intent to install a fire sprinkler system. If a system will be installed, residential or quick response sprinklers shall be used. The sprinkler system may be connected to the domestic water supply, provided the required design density can be met. Be advised that Tucson Water will not allow a residential sprinkler system to be supplied by a 5/8" meter. A minimum of ¾" meter will be required by Tucson Water. Residential fire sprinkler system shall be installed in accordance with the 2018 IFC and NFPA 13D.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/13/2019 AVAUGHN1 APPROVAL SHELF Completed
03/13/2019 AVAUGHN1 OUT TO CUSTOMER Completed
03/13/2019 AVAUGHN1 REJECT SHELF Completed