Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T19CM00626
Parcel: 11522129A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM00626
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/13/2019 ROBERT SHERRY WATER REVIEW Completed
02/14/2019 MARTIN BROWN FIRE REVIEW Approved
02/15/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/15/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The 2018 International Mechanical Code with Local Amendments is the relevant code for this project. Revise the IECC Notes and the ventilation calculations on sheet M3.2 accordingly.
2. The architect-specified range hood requires either a 7" diameter or a 3.25" x 10" duct. Reference: Section 304.1, IMC 2018.
02/15/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A0.1: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the notes.
2. Sheets A0.2.1 through A0.2.4: The City of Tucson requires all lettering to be a minimum of 3/32" in height. Please revise the accessibility notes.
3. Sheets A0.2.1 through A0.2.8: These sheets all indicate "For Reference Only". Some of these details might be required for this project. Please indicate the required details on a sheet not listed as "For Reference Only".
4. Sheet A6.1.3; Keynotes: Add Note 6.29 to the Unit C Proposed Plan and Keynotes. Please indicate to see Sheet A9.1.1 for walls per plan, and provide wall indicators on Sheet A6.1.3.
5. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
02/26/2019 EHAMBLI1 ENGINEERING REVIEW Passed
02/26/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet; E6-1-3. In reference to note 2, could not locate plan E5.2.
Ref; 2018 IBC sec 107.2.1, 2017 NEC
02/26/2019 ELISA HAMBLIN ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/18/2019 QJONES1 APPROVAL SHELF Completed
03/18/2019 QJONES1 OUT TO CUSTOMER Completed
03/18/2019 QJONES1 REJECT SHELF Completed