Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM00575
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/04/2019 | MASHFOR1 | FIRE | REVIEW | Approved | |
02/22/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S1 (General Structural Notes); Geotechnical Study (Page 10): The Geotechnical Study indicates a minimum embedment of 8 feet below grade for the drilled shaft foundation, while the General Structural Notes indicates a minimum of 7 feet below grade. Please coordinate. 2. Structural Calculations: The calculations for the column (and summary page similar to Page 46) for the 15'-6" maximum clearance frame were not located. Please provide. 3. General: Please provide written responses to all review comments. |
02/27/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The manufacturers cut sheet for the Inverters did not have GFCI protection indicated. Please provide the Inverter manufacturer spec's that verify GFCI protection. Ref; 2018 IBC sec 107.2.1, 2017 NEC |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/05/2019 | AVAUGHN1 | APPROVAL SHELF | Completed |
03/05/2019 | AVAUGHN1 | OUT TO CUSTOMER | Completed |
03/05/2019 | AVAUGHN1 | REJECT SHELF | Completed |