Permit Number: T19CM00575
Parcel: 12620001C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM00575
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2019 MASHFOR1 FIRE REVIEW Approved
02/22/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S1 (General Structural Notes); Geotechnical Study (Page 10): The Geotechnical Study indicates a minimum embedment of 8 feet below grade for the drilled shaft foundation, while the General Structural Notes indicates a minimum of 7 feet below grade. Please coordinate.
2. Structural Calculations: The calculations for the column (and summary page similar to Page 46) for the 15'-6" maximum clearance frame were not located. Please provide.
3. General: Please provide written responses to all review comments.
02/27/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The manufacturers cut sheet for the Inverters did not have GFCI protection indicated. Please provide the Inverter manufacturer spec's that verify GFCI protection.
Ref; 2018 IBC sec 107.2.1, 2017 NEC

Final Status

Task End Date Reviewer's Name Type of Review Description
03/05/2019 AVAUGHN1 APPROVAL SHELF Completed
03/05/2019 AVAUGHN1 OUT TO CUSTOMER Completed
03/05/2019 AVAUGHN1 REJECT SHELF Completed