Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T19CM00562
Parcel: 11522129A

Address:
1605 W EL RIO DR

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM00562
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2019 MARTIN BROWN FIRE REVIEW Approved
02/26/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheets A2.1 through A2.3; Type-A Unit Locations: This section indicates to rehabilitate 5% of the units into Type A units (7 total), and 2% of the units into Hearing/Vision Impaired units (3 total). Please clarify that these units will be rehabilitated to meet the ICC/ANSI A117.1 (2009 Edition) Sections 1003 and 1006 on a separate permit.
2. Sheet A3.1; Roof Plans: Please indicate on the plans the weight of the new units on the roof and the weight of the existing units to be removed from the roof.
3. Sheet A6.1.1; Building Plans: Please verify these are first floor plans, and indicate on the plans.
4. Sheet A6.1.1; Building Plans: Please verify on the plans all new windows and doors will use existing frames.
5. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at Eric.Newcomb@tucsonaz.gov
02/26/2019 ROBERT SHERRY WATER REVIEW Completed
02/26/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/27/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show which dwelling units are being revised in this building. Reference: Section 107.2.1, IBC 2018.
2. Provide mechanical ventilation for each dwelling unit that is being revised. Reference: Section R403.6, IECC 2018.
03/06/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Each building is permitted separately and has its own address. Please show the address for each building in order for the plan reviewer to apply fee's and scope of work accurately.
2. Ref; Plan Sheets E1 and E2. Clearly indicate or correlate the 1,2,and 3 bedroom units that are to be renovated per each building.
3. Ref; Plan Sheet E1.1. The Tucson/Pima County Outdoor Lighting Code requires all the lighting on the site or parcel to be included in the lumen calcs, sec 104.2.1(2). Please verify that all the lumens on this parcel are accounted for. The note in the block stating that the Lighting inside the dotted area is by separate permit is confusing.
Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/14/2019 QJONES1 APPROVAL SHELF Completed
03/14/2019 QJONES1 OUT TO CUSTOMER Completed
03/14/2019 QJONES1 REJECT SHELF Completed