Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM00554
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/28/2019 | NICHOLAS ROSS | ZONING | REVIEW | Needs Review | |
| 01/28/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide exhaust for the four copy rooms. Reference: Table 403.3.1.1, IMC 2018. |
| 01/28/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 01/28/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/28/2019 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Please provide written responses to plan review comments: 1. Please provide a listing of the adopted codes as the basis of design; The adopted codes are: 2018 IBC, IMC, IPC, IEBC, IFC, IFGC, 2017 NEC. 2. Please provide an attachment detail of the diagonal wall bracing to the roof structure. IBC 107.2.1 3. Indicate the method of attachment to the slab for new walls. 4. Specify and label the location of the drinking fountain, provide elevation view of hi/lo drinking fountain. IBC TABLE 2902.1 5. Provide plumbing wall elevation of ADA fixtures, lavs where plumning fixtures are being replaced. ICC A117.1-2009 |
| 01/28/2019 | NROSS1 | ENGINEERING | REVIEW | Needs Review | |
| 01/28/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the cycle time to limit the water flow to 0.25 gallons per cycle (i.e. 30 seconds at 0.5.GPM) |
| 01/28/2019 | GPERU1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |