Permit Number: T19CM00554
Parcel: 12201001B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM00554
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2019 NICHOLAS ROSS ZONING REVIEW Needs Review
01/28/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide exhaust for the four copy rooms. Reference: Table 403.3.1.1, IMC 2018.
01/28/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Needs Review
01/28/2019 MARTIN BROWN FIRE REVIEW Approved
01/28/2019 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change Please provide written responses to plan review comments:
1. Please provide a listing of the adopted codes as the basis of design; The adopted codes are: 2018 IBC, IMC, IPC, IEBC, IFC, IFGC, 2017 NEC.
2. Please provide an attachment detail of the diagonal wall bracing to the roof structure. IBC 107.2.1
3. Indicate the method of attachment to the slab for new walls.
4. Specify and label the location of the drinking fountain, provide elevation view of hi/lo drinking fountain. IBC TABLE 2902.1
5. Provide plumbing wall elevation of ADA fixtures, lavs where plumning fixtures are being replaced. ICC A117.1-2009
01/28/2019 NROSS1 ENGINEERING REVIEW Needs Review
01/28/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the cycle time to limit the water flow to 0.25 gallons per cycle (i.e. 30 seconds at 0.5.GPM)
01/28/2019 GPERU1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed