Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T19CM00530
Parcel: 12620001C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM00530
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2019 MARTIN BROWN FIRE REVIEW Approved
02/15/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S1 (General Structural Notes); Geotechnical Study (Page 10): The Geotechnical Study indicated a minimum embedment of 8' below grade for the drilled shaft foundation, while the General Structural Notes (Foundation Section) indicated a minimum of 7'-0" below grade. Please coordinate.
2. Sheet S2; Column/Footing Schedule: Please verify the column design calculations for the maximum clear height of 15'-6" is included in the calculations.
3. General: Please provide written responses to all review comments.
02/25/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a grounding detail or indicate on the line diagrams type of GEC and electrodes used for grounding the 150KVA transformer. NEC 250.30
2. Ground fault protection information was not found in the manufacturer cut sheet specifications for the inverter, s, utilized. Please verify. And provide data from the manufacturer on the plans. NEC 690.41B.
Ref; 2018 IBC sec 107.2.1, 2017 NEC.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/27/2019 AVAUGHN1 OUT TO CUSTOMER Completed