Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T19CM00524
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/25/2019 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 01/29/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Indicate conduit, conductor sizes and types for the service secondary conductors. 2. Indicate the OCPD sizes and types in the service equipment. 3. The panel identification per keyed note 13, 17, does not correlate with the panel schedules. Also the panel schedule shows 3 -50 amp OCPD's, and the one line only shows 2. Please clarify. 4. Neutral conductors need to be bonded at the service equipment only. 2017 NEC 250.24c. Ref; 2018 IBC sec 107.2.1, 2017 NEC |