Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2019 MARTIN BROWN FIRE REVIEW Approved
02/14/2019 LOREN MAKUS ENGINEERING REVIEW Passed
02/25/2019 NICHOLAS ROSS ZONING REVIEW Reqs Change DP18-0310 must be approved before building permit gets approved.
02/28/2019 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Completed
02/28/2019 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL – COMMERCIAL
Please confirm that all exterior light fixtures have a maximum color temperature rating of 3,500K. It appears that at least one fixture (S1H) exceeds that limitation. Ref. 2012 City of Tucson/Pima County Outdoor Lighting Code 402.1.
02/28/2019 KROBLES1 WATER REVIEW Completed
02/28/2019 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change BUILDING – COMMERCIAL
On sheet A5.0, Exterior Window Assembly, note 6 states that the U-factor shall not exceed 0.70 max. Change this to 0.50 max. for fixed fenestration, 0.65 max. for operable fenestration, and 0.83 for entry doors. Ref. 2018 IECC Table C402.4.
Detail 3/A5.2 shows stucco for wall system 1 terminating a joint width above sidewalk. This does not comply with the 2018 IBC 2512.1.2 where stucco weep screeds shall be located at or below foundation plate lines and minimum 2” above paved surfaces. This is correctly specified by note 1 in the description for Exterior Wall Assembly 1 on sheet A5.0. The Architect may propose an alternative weep screed detail by an Appeal to the Building Official. Find the Appeal to the Building Official form under the link “All Application Forms & Submittal Requirements” on the City of Tucson Planning & Development Services website.
New exterior wall infills shall be insulated to comply with the 2018 IECC Table C402.2. For steel framed construction the minimum insulation is R-13 cavity insulation between studs and a layer of continuous R-5 insulation. Place this note on the floor plan, sheet A1.0.
According to the Plumbing Schedule on kitchen equipment sheet K-3, two combi ovens and a relocated coffee brewer will require domestic cold water connections. Per 2018 IPC section 608.14 these appliances require backflow protection. Please have the kitchen equipment sheets revised to identify how this will be achieved. The note “per local codes” in the requirements column of the schedule is not sufficient.
Submit a Special Inspection Certificate for special inspections required, i.e. epoxy anchors. You can find this Certificate on the City of Tucson Planning & Development Services website.
02/28/2019 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – COMMERCIAL
Please confirm that the faucet selected for LAV-1 in the Plumbing Fixture Schedule, sheet MP1, will dispense no more than 0.25 gallon per metering cycle. Ref. City of Tucson amendment to the 2018 IPC, new section 412.11.
Please confirm whether or not the new mop sink will be used for grease water spills within the kitchen area. If the mop sink will be used for kitchen area spills and floor cleaning it shall be connected to the grease waste line for this facility per the City of Tucson amendment to the 2018 IPC section 1003.3.4.1.
The new floor sink in the kitchen shall be routed to the grease waste line and not the main sanitary line for the building. Ref. City of Tucson amendment to the 2018 IPC section 1003.3.4.1.
The new hand sinks in the kitchen shall be routed to the grease waste line unless a sign is posted over each hand sink “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED.” Ref. City of Tucson amendment to the 2018 IPC section 1003.3.4.1.