Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM00416
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/22/2019 | NICHOLAS ROSS | ZONING | REVIEW | Approved | |
| 01/22/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a design (structural & mec for the relocation of the HVAC unit. Show the ductwork and provide the air balancing data. 2. Provide the windw schedule and show that the new window complies with the 2018 IECC. |
| 01/22/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 01/22/2019 | NROSS1 | ENGINEERING | REVIEW | Passed | |
| 01/22/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.0; Special Inspections Note: There is a special inspection required for the epoxy anchors (see Detail 5/A2.0). 2. Sheet A2.0; Wall Types: Wall Type B indicates a partition wall to 6" above the ceiling. Detail 4/A2.0 indicates the same wall extending to the structure above. If wall does stop above the ceiling, please provide a detail indicating the top of wall bracing, including bracing size and spacing, and connection of bracing to top of partition and to roof above. Please coordinate. |
| 01/22/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/22/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/23/2019 | MASHFOR1 | FIRE | REVIEW | Approved | |
| 01/23/2019 | GPERU1 | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide written responses to all plan review comments: 1. Provide the electric branch circuit wiring diagram to the relocated mechanical units; show maintenance outlet(s) and disconnect. NEC 440 |