Permit Number: T19CM00416
Parcel: 11005014C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM00416
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2019 NICHOLAS ROSS ZONING REVIEW Approved
01/22/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide a design (structural & mec for the relocation of the HVAC unit. Show the ductwork and provide the air balancing data.
2. Provide the windw schedule and show that the new window complies with the 2018 IECC.
01/22/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
01/22/2019 NROSS1 ENGINEERING REVIEW Passed
01/22/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Special Inspections Note: There is a special inspection required for the epoxy anchors (see Detail 5/A2.0).
2. Sheet A2.0; Wall Types: Wall Type B indicates a partition wall to 6" above the ceiling. Detail 4/A2.0 indicates the same wall extending to the structure above. If wall does stop above the ceiling, please provide a detail indicating the top of wall bracing, including bracing size and spacing, and connection of bracing to top of partition and to roof above. Please coordinate.
01/22/2019 ROBERT SHERRY WATER REVIEW Completed
01/22/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/23/2019 MASHFOR1 FIRE REVIEW Approved
01/23/2019 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide written responses to all plan review comments:
1. Provide the electric branch circuit wiring diagram to the relocated mechanical units; show maintenance outlet(s) and disconnect. NEC 440