Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T19CM00396
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Clarify the connected loads or input ratings for each appliance. Southwest Gas, the local gas utility provides natural gas with an energy content of approximately 1,000 BTU per cubic foot. Reference: Section 402.1, IFGC 2018. |
| 04/19/2019 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | According to Tucson Water, the water pressure range for the address is 48 to 55 PSI. |
| 04/19/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Note: this submittal contained no revised mechanical plans. 1. Verify the maximum U-value that will be accepted for the curtain walls. The COMcheck component description shows 0.28 BTU/hr ft^2 F but the specifications allow a U-value of 0.66 BTU/hr ft^2 F. Reference: SectionC303.1.3, IECC 2018. 2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1, IECC 2018. 3. Verify that the freezer complies with the requirements of Section C403.10.2, IECC 2018. 4. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson. 5. Provide note 4 for detail 1/M301 (Rooftop Unit Detail). Reference: Section 107.2.1, IBC 2018. |
| 04/24/2019 | QJONES1 | ZONING | REVIEW | Needs Review | |
| 04/24/2019 | RMCCOY1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/24/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 04/24/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 04/24/2019 | QJONES1 | REJECT SHELF | Completed |