Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM00396
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/19/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/27/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Note: this submittal contained no revised plumbing plans. 1. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Provide a site plan showing the installation of the water service to the building and the installation of the building sewer. Reference: Sections 104.2 and 107.2.1, IBC 2018. 2. Coordinate the source and location of the irrigation water meter, backflow preventer, and service piping with the civil design. 3. Verify that the specified sensor faucet for the public lavatories has an automatic time-out so that it will dispense a maximum of 0.25 gallons per metering cycle. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 4. Verify that all of the vents (except for the island sink vents) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Sections 202 (horizontal pipe) and 905.4, IPC 2018. 5. Clarify which roof drains are primary and which are secondary. Primary roof drains may not discharge onto a sidewalk. 6. Clarify the connected loads or input ratings for each appliance. Southwest Gas, the local gas utility provides natural gas with an energy content of approximately 1,000 BTU per cubic foot. Reference: Section 402.1, IFGC 2018. |
| 03/27/2019 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Note: this submittal contained no revised plumbing plans. 1. The water meter will not be located within the building. See the civil plans for the location of the water meter. 2. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water (see the development package). Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf 3. Contact Tucson Water for new water services, not the City of Mesa. They are located at 201 N Stone Ave., 520-791- 5164. 4. According to Tucson Water, the water pressure range for the address is 48 to 55 PSI. |
| 04/04/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; 2012 Tucson/Pima County Outdoor Lighting Code. The following information needs to be on the plans as well as inventory, locations, as stated in the Code section 104. (a) A complete luminaire schedule that includes all the exterior luminaires. Include a description of the illuminating devices, fixtures, lamps (color temp), supports, reflectors, shielding. (b) A statement of the lighting area and option used, Table 401.1. (c) Parcel size in acres, maximum shielded and unshielded allowed per table 401.1. (d) Total proposed shielded (full cut-off) and unshielded lumens. (e) Any exceptions used. (f) A note indicating whether or not a special inspection is needed per section 106.2. 2. Also see chapter 4 for lumen restrictions and curfew requirements for unshielded luminaires, and section 402.1 for color temperature restrictions. 3. Provide a note on the power plan that addresses NEC art 517.13 for Exam rooms and or Patient Care Areas as defined by 517.2 NEC. Reference; 2012 Tucson/Pima County Outdoor Lighting Code. |
| 04/04/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; 2012 Tucson/Pima County Outdoor Lighting Code. The following information needs to be on the plans as well as inventory, locations, as stated in the Code section 104. (a) A complete luminaire schedule that includes all the exterior luminaires. Include a description of the illuminating devices, fixtures, lamps (color temp), supports, reflectors, shielding. (b) A statement of the lighting area and option used, Table 401.1. (c) Parcel size in acres, maximum shielded and unshielded allowed per table 401.1. (d) Total proposed shielded (full cut-off) and unshielded lumens. (e) Any exceptions used. (f) A note indicating whether or not a special inspection is needed per section 106.2. 2. Also see chapter 4 for lumen restrictions and curfew requirements for unshielded luminaires, and section 402.1 for color temperature restrictions. 3. Provide a note on the power plan that addresses NEC art 517.13 for Exam rooms and or Patient Care Areas as defined by 517.2 NEC. Reference; 2012 Tucson/Pima County Outdoor Lighting Code. |
| 04/08/2019 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Section Manager PROJECT: Bio-Life Plasma Service Center T19CM00396 Building Plan (2nd Review) TRANSMITTAL DATE: April 8, 2019 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Until all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 04/08/2019 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/19/2019 | AVAUGHN1 | APPROVAL SHELF | Completed |
| 04/19/2019 | AVAUGHN1 | OUT TO CUSTOMER | Completed |
| 04/15/2019 | PMARTIN1 | REJECT SHELF | Completed |