Review Details: CELL TOWER/ANTENNAS

Permit Number - T19CM00382
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2019 MARTIN BROWN FIRE REVIEW Approved
01/31/2019 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide written responses to plan review comments:
1. Cite the adopted 2017 Edition of the National Electric Code and reference Art. 250.106 for the installation of the lightning rod.
2. Provide grounding and bonding details for the lightning rod. NEC Art. 250-106.
01/31/2019 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change Please provide written responses to all plan review comments.
1. Please cite the 2018 IBC as this is the adopted edition of the code for all structural design and special inspection. IBC 107.2.1
2. Provide a list of required Special Inspections for the installation of the monopole extension as applicable to this project, rather than an overall list of inspections that do not seem to be associated with the scope of work. IBC 107.2.1, 1704.2.
3. Provide note on the plans that the reinstallation of antennas and appurtenances will be under separate permit. IBC 107.2.1
02/07/2019 JOHN VAN WINKLE ENGINEERING REVIEW Passed
02/07/2019 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Denied Prior to permitting, the project will require an Administrative Special Exception review (Directors Procedure Speical Exception for Wireless Communication Facilities) due to the proposed increase in tower height. The application can be submitted to PDSD Entitlements Section on the 3rd Floor of 201 N. Stone Avenue. Link to correct application on the City website is:
https://www.tucsonaz.gov/files/pdsd/forms/WCF_PDSD_Director_50_Notice_Procedure_Application.pdf
02/07/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T19CM00382 - Existing Cell Tower Location (TEP Station Parcel)
Cell Tower - 10' Pole Extension (1st Review)
1130 N. Craycroft Road - C-2 Zoning

TRANSMITTAL DATE: February 7, 2019

DUE DATE: February 12, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: Zoning has reviewed the application permit and plans but cannot approve them at this time. Prior to zoning approval a special exception review and approval through PDSD director's decision is required.

Contact Peter McLaughlin at 520-837-4898 or Peter.McLaughin@tucsonaz.gov for information on the special exception process.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Plans
02/11/2019 AMARTIN1 COMMUNICATIONS REVIEW Completed