Permit Number: T19CM00367
Parcel: 12620001C

Address:
3455 E ZOO CT

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM00367
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/15/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
1. 2017 NEC 705.32, " Where ground fault protection is used, the output of an interactive system Shall be connected to the supply side of the ground fault protection".

Final Status

Task End Date Reviewer's Name Type of Review Description
02/21/2019 AVAUGHN1 OUT TO CUSTOMER Completed