Permit Number: T19CM00339
Parcel: 13312004H

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM00339
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PZSE Structural Calculations; Pages 10 through 13: Please provide full size drawings for the various array layout plans and the ballast quantities and locations. In addition, provide connection details for the arrays as required.
2. Schneider Structural Calculations: Please provide a full size drawing for the various array layout plans and the locations of the additional screws required for attachment of the PV panels to the roof.
3. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
02/05/2019 MARTIN BROWN FIRE REVIEW Approved
02/11/2019 JOHN VAN WINKLE ENGINEERING REVIEW Passed
02/14/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. REF; Riser and line diagrams.
(a) Plan Sheet 2018092 shows the electrical service rated at 600 amps. The three -line diagram shows the service rated at 800 amps. Please clarify.
(b) The picture of the existing service shows only three disconnect switches installed and the three-line diagram shows four and a main. Provide information on the plans to clarify the requirements needed to accommodate the installation of the additional switches.
2. Verify that the inverter is equipped with ground fault protection. Not specified on the spec sheet. NEC art 690.5.
3. Provide all the plan sheets as described on the drawing description on the cover sheet, and include the numbers on the drawings.
4. Provide the PV modules racking system details.
5. Provide grounding details for the racking system and modules.

6. Provide a permanent plaque or directory per NEC section 705.10 at each service on the premises.

7. Ref; Plan sheet 2018091 and the 3 -line diagram plan.

(a) Identify all the areas where the PV modules are mounted apart from the roof area.
(b) Are all the DC source circuits installed in EMT conduit as the wire schedule shows to the inverter?
(c) The equipment layout shows 9 string home runs to the inverter and the 3-line shows 8. Please clarify.
Ref; 2012 IBC sec 107.2.1, 2011 NEC art 230, 690, 705.
02/14/2019 DAVID RIVERA ZONING REVIEW Reqs Change Revise on the site plan the annotation PROPOSED MULTI-PURPOSE BUILDING to "Exisitng Multi-Purpose Building Bldg. 4"

Final Status

Task End Date Reviewer's Name Type of Review Description
02/19/2019 TWEIDEM1 APPROVAL SHELF Completed
02/19/2019 TWEIDEM1 OUT TO CUSTOMER Completed
02/19/2019 TWEIDEM1 REJECT SHELF Completed