Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM00300
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/15/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Structural Calculations: The carport structure page indicates columns at 18'-0" o.c., with a cantilevered beam spanning 17' and the roof deck cantilevering 9' at each end. Please verify allowable stresses and deflections are not exceeded. 2. Structural Calculations; Main Beam: Please verify the frames are a maximum 18'-0" o.c., with a 17'-0" cantilever beam. 3. General: Please provide full size structural sheets. Information should include structural general notes, material strengths, member sizes, connections, details and sections as required, and alternate foundation systems. 4. General: Please provide written responses to all review comments. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/19/2019 | KROBLES1 | OUT TO CUSTOMER | Completed |