Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T19CM00295
Parcel: 141020190

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM00295
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change Please provide written responses, in addition to corrected plans to all plan review comments.
1. All plan sheets must be sealed by a professional registrant. IBC 107.2.1
2. Sh. AB04 The cross section of the concrete bench seat indicates that a column and weld plate are sitting on it. The columns must be supported on a conctete footing that is 12" into undisturbed soil. Provide a detail for bench seet footings. IBC 1809.4
3. Please specify the total number of ramadas that will be constructed. IBC 107.2.1
4. The Structural Calculations show a footing size of 4'-0" SQ footing, but SH. E102 shows a 3'-6" SQ footing. Please size the footings based on the structrual calcs.
5. The SPECIAL INSPECTION CERTIFICATE must be filled in and signed before the permit can be issued. IBC 1704.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/29/2019 AMARTIN1 OUT TO CUSTOMER Completed