Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/28/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Please provide written responses, in addition to corrected plans to all plan review comments. 1. All plan sheets must be sealed by a professional registrant. IBC 107.2.1 2. Sh. AB04 The cross section of the concrete bench seat indicates that a column and weld plate are sitting on it. The columns must be supported on a conctete footing that is 12" into undisturbed soil. Provide a detail for bench seet footings. IBC 1809.4 3. Please specify the total number of ramadas that will be constructed. IBC 107.2.1 4. The Structural Calculations show a footing size of 4'-0" SQ footing, but SH. E102 shows a 3'-6" SQ footing. Please size the footings based on the structrual calcs. 5. The SPECIAL INSPECTION CERTIFICATE must be filled in and signed before the permit can be issued. IBC 1704. |